TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumptioon 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.74 inches deep. It weighs 1.07 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
IEC contactor, TeSys Deca, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 12VDC coil
IEC contactor, TeSys Deca, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 12VDC coil
SKU: 172555729
Category: Automation & Control
Reviews (0)
Be the first to review “IEC contactor, TeSys Deca, nonreversing, 12A, 7.5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 12VDC coil” Cancel reply
Related products
TeSys Deca thermal overload relays – 23…32 A – class 10A
TeSys Deca thermal overload relays - 23...32 A - class 10A
Harmony XB4, Light block with body/fixing collar, metal, blue, integral LED, 24 V AC/DC, 2 NO
Harmony XB4, Light block with body/fixing collar, metal, blue, integral LED, 24 V AC/DC, 2 NO
communication module Profibus DP V1, Altivar, 12Mbps, 1 female SUB D9 connector
communication module Profibus DP V1, Altivar, 12Mbps, 1 female SUB D9 connector
variable speed drive, Altivar 212, 18.5kW, 25hp, 240V, 3 phases, without EMC, IP21
variable speed drive, Altivar 212, 18.5kW, 25hp, 240V, 3 phases, without EMC, IP21
Set of 2 heavy duty vertical rails for fixing of chassis and cross rails-2000 mm
Set of 2 heavy duty vertical rails for fixing of chassis and cross rails-2000 mm
Mechanical alternator, Square D Pumptrol, closed tank, NEMA 1, screw in bushing, 4NC DPST DB contacts
Mechanical alternator, Square D Pumptrol, closed tank, NEMA 1, screw in bushing, 4NC DPST DB contacts
Reviews
There are no reviews yet.